Is this Charge Controller Sized Correctly?

Is this Charge Controller Sized Correctly?

Hello,

Getting Ready to set up some solar for my Van. I already have the Solar Panels, and am ready to buy the Charge Controller. Just wanted to run in by you all to verify If the one I have selected is sized appropriately.

I have 12x Renology 100D-s Panels (https://www.renogy.com/template/files/Specifications/RNG-100D-S_spec.pdf)

Battery (not bought Yet, but will be 12V Lithium Bank)

Panels will be Wired 6 Parallel Sets of 2 Panels in series.

Here is the charge Controller That I was thinking (100/50 Model): https://www.victronenergy.com/solar-charge-controllers/smartsolar-100-30-100-50#pd-nav-image

If someone could assist with helping me verify if this charge controller is large enough, that would be Awesome!!

Edit: I'll Initially have 12 Panels, but I'd also like to size with ability to Add one more Parallel set (of two Panels in Series) I believe I will have room.

Edit2: Thanks for everyone's input so far! Charge Controller is too small, unless I were to utilize more than one controller, otherwise would either need to go to higher voltage battery bank and or larger controller.

submitted by /u/davcenmt2
[visit reddit] [comments] https://ift.tt/2C3RFro